Interscan Corporation
4590 Ish Drive #110
Simi Valley, CA 93063-7682
TOLL FREE: (800) 458-6153 (US & Canada)   PHONE: (818) 882-2331  FAX: (818) 341-0642
E-Mail: info@gasdetection.com   Web site: www.gasdetection.com
All Categories > Gas Detection Instruments And Systems > Multipoint (3 or more points) Continuous Monitoring Systems > Three Point Monitoring Systems - PLC Series - Formaldehyde > Item # SRPLC316-2.00m  


Item # SRPLC316-2.00m, Three Point Monitoring Systems - PLC Series - Formaldehyde


PLC Multipoint Monitoring Systems include:
  • Displays real time gas concentrations in ppm
  • Dedicated sensor, sample pump, and digital flow switch for each monitoring location
  • All control and display functions at easy-to-use operator interface
  • User adjustable, LO & HI alarm set points, activating dedicated relays for each monitoring location
  • Stackable tower lights for LO, HI, and fault alarms, and Piezo horn for HI alarm common to all channels
  • Alarm event and time tracking, last time calibrated tracking, specific for each sensor
  • Pump vacuum fault detection and fault display
  • System packaged in wall-mountable NEMA 12 enclosure
  • 4-20 mA output - dedicated for each point







Specifications

Accuracy

± 2.0% of reading, ± 1 least significant digit. (Limited to accuracy of calibration standard)

Repeatability

± 0.5% of full scale

Minimum Detectability

1.0% of full scale

Linearity

± 1.0% of full scale

Zero Drift

± 1.0% of full scale (24 hours)

Span Drift

Less than ± 2.0% of full scale (24 hours)

Calibration

Against standard gas mixture, or via INTERSCAN's Electronic Calibration Service.

Lag Time

Less than 1 second

Range

0-2.00 ppm

Resolution

0.01 ppm

Gas

Formaldehyde (HCHO)

Number of Detection Points

3

Application

Continuous

Includes Auto Zero

Yes

Note

The zero and span drift specifications assume that the analyzer is equilibrated, and is at constant temperature, with a properly maintained sensor.